NHTSA Recall 18V504000: Electrical system: wiring
Cummins Inc. reported this safety recall to NHTSA on , covering an estimated 921 vehicles. It affects 2015–2018 Cummins Power Generation Generator Set.
| NHTSA campaign | 18V504000 |
|---|---|
| Component | ELECTRICAL SYSTEM › WIRING |
| Report received | July 31, 2018 |
| Owner notification | September 21, 2018 |
| Initiated by | Manufacturer |
Defect
Cummins Inc. (Cummins) is recalling certain 2015-2018 Power Generation trailers, models C60D6R, C150D6R, C80D6R, C100D6R, C200D6R, C300D6R, C150D2R3 and C200D2Re, 2016-2018 C275D2Re and 2018 C70D2Re and C100D2Re. These generator sets may have incorrectly wired remote emergency stop and remote start connections causing the remote stop to not function and shut down the generator as intended.
Safety risk
If the unit does not shut down as expected when the remote E-stop is activated, it can increase the risk of injury.
Remedy
Cummins will notify owners, and dealers will inspect the remote E-stop function and, if necessary, repair or replace the remote E-stop/remote start switch panel, free of charge. The recall is expected to begin September 2018. Owners may contact Cummins customer service at 1-800-286-6467.
Notes
Owners may also contact the National Highway Traffic Safety Administration Vehicle Safety Hotline at 1-888-327-4236 (TTY 1-800-424-9153), or go to www.safercar.gov.
Vehicles covered by recall 18V504000
Being listed here means the campaign covers the model year, not that every car was built with the defect or is still unrepaired. Enter your VIN above to check your specific vehicle. Recall repairs are free at authorised dealers. Source: NHTSA, October 2026.